RU EN
Request a quote

Fox ESS · three-phase grid inverter

Fox ESS T Series (G3) inverter, 3–25 kW

The most widely used three-phase range: twelve ratings from 3 to 25 kW. One housing size across the whole series, so the installer does not have to rework switchboard space when the rating changes.

3–25 kW grid-tied 2 MPPT up to 98.6% IP65 12 ratings

Twelve ratings

Fine steps: 3, 4, 5, 6, 8, 10, 12, 15, 17, 20, 23 and 25 kW. Match the inverter to the array precisely without paying for unused headroom.

Wide MPPT window

A 140–1000 V range and 140 V start-up voltage — long strings and an early start even in overcast weather.

One housing throughout

Dimensions of 370×480×183.5 mm are identical from T3 to T25: standard switchboard space regardless of rating.

98.6% efficiency

Maximum power point tracking runs at 99.8%. Conversion losses stay low across the whole load range.

On requestwholesale price depends on volume
Request a price

Shipped from stock in Krasnodar across Russia. Send us the array size and grid phase configuration — our engineer will check the inverter selection and string layout before dispatch.

Model range and electrical data

← scroll the table →

ModelMax. PV array, WRated power, WMax. apparent power, VARated current, AMax. current, AStrings per tracker
T3-G3 4500 3000 3300 4,3 4,8 1+1
T4-G3 6000 4000 4400 5,8 6,4 1+1
T5-G3 7500 5000 5500 7,2 8,0 1+1
T6-G3 9000 6000 6600 8,7 9,6 1+1
T8-G3 12000 8000 8800 11,6 12,8 1+1
T10-G3 15000 10000 11000 14,5 15,9 1+1
T12-G3 18000 12000 13200 17,4 19,1 1+1
T15-G3 22500 15000 16500 21,7 23,9 2+2
T17-G3 25500 17000 18700 24,6 27,1 2+2
T20-G3 30000 20000 22000 29,0 31,9 2+2
T23-G3 34500 23000 25300 33,3 36,7 2+2
T25-G3 37500 25000 27500 36,2 39,9 2+2

Specifications and operating conditions

← scroll the table →

Max. input voltage 1100 V DC
Start-up voltage 140 V
Rated input voltage 600 V
MPPT voltage range 140–1000 V
Max. input / short-circuit current 14 A / 18.2 A (T3–T12) · 28 A / 36.4 A (T15–T25)
MPP trackers 2
Efficiency: MPPT / European / max. 99.8% / 97.8% / 98.6%
Grid 3/N/PE · 220/380, 230/400, 240/415 V · 50/60 Hz
Power factor / THDi 1 (adjustable to 0.8) / <3%
Dimensions (W×H×D) / weight 370 × 480 × 183.5 mm · 17–21 kg
Cooling / topology natural convection or fan · transformerless
Operating conditions −25…+60 °C · up to 3000 m · IP65 · noise <30…<55 dB
Night consumption <3 W
Monitoring and communication Wi-Fi / 4G (optional) · RS485, meter, DRM, Estop · LCD, app, web portal
Protection insulation monitoring, residual current monitoring, DC reverse polarity protection, anti-islanding, AC short-circuit and overcurrent protection, AC overvoltage protection, PV string current monitoring; DC/AC type II SPD, DC switch and AFCI optional
Standards EN 62109-1/-2 · EN 61000-6-1/2/3/4 · EN 50549-1 · VDE-AR-N 4105 · CEI 0-21 · RD 1699 · AS/NZS 4777.2

Documents

Official manufacturer datasheets. Installation manuals and certificates are supplied with the order — ask us and we will send them the same day.