RU EN
Request a quote

Fox ESS · single-phase grid inverter

Fox ESS G Series inverter, 7–10.5 kW

The top of the single-phase grid range: three MPPT trackers and 97.8% peak efficiency. For sites with a single-phase supply and a large roof — houses, small production units, shops and farm buildings.

7–10.5 kW grid-tied 3 MPPT up to 97.8% IP65 19 kg

Three trackers

The array can be split into three groups with different orientation and tilt — unusual flexibility for a single-phase inverter.

Most from a single phase

Up to 10.5 kW without moving to three phases, so there is no need to renegotiate the grid connection.

97.8% efficiency

The best figure among the Fox ESS single-phase grid-tied series.

Room for oversizing

Up to 15,750 W of panels on a 10.5 kW inverter — DC oversizing lifts morning and evening output.

On requestwholesale price depends on volume
Request a price

Shipped from stock in Krasnodar across Russia. Send us the array size and grid phase configuration — our engineer will check the inverter selection and string layout before dispatch.

Model range and electrical data

← scroll the table →

ModelMax. PV array, WRated apparent power, VAMax. apparent power, VARated current, AMax. current, A
G7 10500 7000 7700 30,4 33,5
G8 12000 8000 8800 34,8 38,3
G9 13500 9000 9900 39,1 43,0
G10 15000 10000 10500 43,5 45,7
G10.5 15750 10500 10500 45,7 47,7

Specifications and operating conditions

← scroll the table →

Max. / min. input voltage 600 / 80 V DC
Start-up voltage 120 V
Rated input voltage 360 V
MPPT voltage range 80–550 V
Max. input / short-circuit current 14 A / 18 A
MPP trackers / strings per tracker 3 / 1
Efficiency: MPPT / European / max. 99.0% / 97.4% / 97.8%
Grid 220/230/240 V, 50/60 Hz
Dimensions (W×H×D) / weight 380 × 440 × 167 mm · 19 kg
Cooling / topology natural convection · transformerless
Operating conditions −25…+60 °C · up to 3000 m · IP65 · <30 dB
Monitoring and communication Wi-Fi / 4G (optional) · RS485, meter/CT, DRM · LCD, app, web portal
Protection insulation monitoring, residual current monitoring, DC reverse polarity protection, anti-islanding, AC short-circuit and overcurrent protection, AC overvoltage protection; type II SPD, DC switch and AFCI optional
Country of manufacture China
Standards EN 62109-1/-2 · EN 61000-6-1/3 · AS/NZS 4777.2 · G99 · NB/T 32004